Parker BA-DME Breathing Air Purification Unit


The BA-DME purification unit meets European Pharmacopoeia requirements for compressed air production.






Parker BA-DME breathing air purifiers with CO/CO2 purification – treated air meets the European Pharmacopoeia requirements for medical compressed air.

Producing clean air is a basic requirement for every hospital and pharmaceutical factory. BA-DME breathing air purification packages include integrated filtration and purification stages, and the air they produce meets the European Pharmacopoeia requirements for medical compressed air. The purification units are a suitable solution when the need for breathing air is moderate.

We assist in proper plant sizing

  • The compressed air system designer makes their own calculations based on the request for quotation.
  • Additionally, we need information on how much medical compressed air is required and at what pressure.
  • If it is a renovation project, we can perform a capacity measurement for the old system.

Breathing air purifier cleaning stages

  1. General filtration: Removal of particles down to 1 µm. Maximum residual oil content 0.5 ppm.
  2. Fine filtration: Removal of particles down to 0.01 µm. Maximum residual oil content 0.01 ppm.
  3. Activated carbon filtration: Removal of oil vapors and odors, maximum residual oil content 0.003 ppm.
  4. Heatless regenerated adsorption dryer: Pressure dew point -40°C, partial removal of carbon dioxide (CO2).
  5. Carbon/catalyst purification unit: Reduction of CO levels to comply with breathing air standards through oxidation
  6. Dust filtration: Removal of 99.9999% of particles

European Pharmacopoeia quality requirements for medical air

ImpurityEuropean PharmacopoeiaParker domnick hunter BA DME/BAM series*
Water67 ppm (-45º atmospheric dew point)14 ppm (-58º  atmospheric dew point)
Oil/lubricant0.1 mg/m³0.003 mg/m³
Carbon dioxide (CO2) **< 500 ppm< 500 ppm
Carbon monoxide (CO) ***< 5 ppm< 5 ppm
Nitrogen oxides (NO+NO2)< 2 ppm< 2 ppm
Sulfur dioxide (SO2)< 1 ppm< 1 ppm
*     Independently tested for Parker domnick hunter / Pattinson Scientific Services
**   When the intake concentration is 700 ppm
*** When the intake concentration is 65 ppm